Standard
Configuration |
Optional
Configuration |
Cabinet
|
Welded steel frame, primed and epoxy painted. Reinforced
white epoxy painted aluminum panels with easy access hardware. Water
cooled and split systems can pass through 34” doors. Adjacent
modules connected using heavy steel headers with rolled groove couplings. |
• Stainless steel access panels • Sound
attenuating access panels • Smaller enclosure sizes
• Engineered frames to accommodate special size restrictions
|
Controls
and Safeties
|
Microprocessor controller monitors temperatures and pressures. Manual
reset high and auto reset low refrigerant safeties. Alternating lead/lag
with anti short cycle compressors. Power supply monitor. Keypad interface
for set points, temperatures, pressures and alarms.
|
• Dual pump lead/lag controls • Flooded head pressure
controls • Remote web-based diagnostics • MODBUS
building automation interface • Up to 16 compressors for
load matching
|
Electrical
|
Models can be specified for 208-230, 460, 575 or 380 Volts with
50 or 60 Hz three phase operation. 24 volt control circuit. Single
point power connections.
|
• Panel or remote disconnect • Single phase for
large models • Special voltages
|
Indicators
|
Chiller run status, compressor run hours, active alarm indication,
alarm logging of previous 100 alarms. Water temperature and refrigerant
pressure readouts.
|
• Dry contacts for building automation systems •
Remote panel with flow, temp, and pressures indicators
|
Refrigeration
|
Two independent HFCF R-22 circuits include filter dryer. Service
valves for isolation service and pump down are provided.
|
• Alternate refrigerants • Hot gas bypass capacity
control • Semi-hermetic compressors with staged capacity
control
|
Air Cooled Condensers
|
Enhanced seamless copper tubing. Mechanically bonded aluminum fins.
Integral subcooling. Overload protected TEAO fan motors. Aluminum
fans.
|
• Coated or copper fins for corrosion • Free cooling
module • High ambient and altitude designs • Low
noise fans
|
Water Cooled Condensers
|
Shell and Tube for changeability and increased particle tolerance.
Seamless, enhanced surface copper tubing.
|
• Special construction materials • High pressure
designs • 3-way water regulating valve
|
Evaporators
|
Direct expansion shell & tube design. Closed cell insulation.
|
• Special construction materials • Heat tracing
for low ambients • Dual circuit evaporators
|
Compressors
|
Hermetic scroll or reciprocating types. Internal overload protection.
Crankcase heaters and service valves.
|
• Semi-hermetic compressors • Multiple circuit designs
• Dual pump lead/lag operation
|
Piping
|
Refrigerant piping is rigid copper with service valves. Insulated
suction lines. Water circuit is insulated seamless heavy grade copper.
|
• Alternative materials for special fluids and corrosion resistance
|
Warranty and Certifications
|
One year parts, five year limited compressor warranty. ETL Listed.
MEA-386-92E for metropolitan New York.
|
• Extended parts & labor warranty • Guaranteed
emergency response • Factory start-up and maintenance
|