“Manhattan Modular” chillers allow easy field assembly of large tonnage systems, without the need for heavy rigging and construction. Quiet operation and highly reliable components and controls provide dependable air-conditioning and more precise load balancing.

Headers are heavy steel tubing with precision grooves. Modules are attached using reliable Victaulic couplings. All slave modules are connected to the Master Module which houses centralized controls and power connections for the bank of chillers.

Modular Chillers solve problems associated with renovation of older buildings where often, they are the only practical choice.

Manhattan Modular - Standard and Optional Configurations

 
Standard Configuration
Optional Configuration
Cabinet
Welded steel frame, primed and epoxy painted. Reinforced white epoxy painted aluminum panels with easy access hardware. Water cooled and split systems can pass through 34” doors. Adjacent modules connected using heavy steel headers with rolled groove couplings. • Stainless steel access panels
• Sound attenuating access panels
• Smaller enclosure sizes
• Engineered frames to accommodate special size restrictions
Controls and Safeties

Microprocessor controller monitors temperatures and pressures. Manual reset high and auto reset low refrigerant safeties. Alternating lead/lag with anti short cycle compressors. Power supply monitor. Keypad interface for set points, temperatures, pressures and alarms.
• Dual pump lead/lag controls
• Flooded head pressure controls
• Remote web-based diagnostics
• MODBUS building automation interface
• Up to 16 compressors for load matching
Electrical
Models can be specified for 208-230, 460, 575 or 380 Volts with 50 or 60 Hz three phase operation. 24 volt control circuit. Single point power connections.
• Panel or remote disconnect
• Single phase for large models
• Special voltages
Indicators
Chiller run status, compressor run hours, active alarm indication, alarm logging of previous 100 alarms. Water temperature and refrigerant pressure readouts.
• Dry contacts for building automation systems
• Remote panel with flow, temp, and pressures indicators
Refrigeration
Two independent HFCF R-22 circuits include filter dryer. Service valves for isolation service and pump down are provided.
• Alternate refrigerants
• Hot gas bypass capacity control
• Semi-hermetic compressors with staged capacity control
Air Cooled Condensers
Enhanced seamless copper tubing. Mechanically bonded aluminum fins. Integral subcooling. Overload protected TEAO fan motors. Aluminum fans.
• Coated or copper fins for corrosion
• Free cooling module
• High ambient and altitude designs
• Low noise fans
Water Cooled Condensers
Shell and Tube for changeability and increased particle tolerance. Seamless, enhanced surface copper tubing.
• Special construction materials
• High pressure designs
• 3-way water regulating valve
Evaporators
Direct expansion shell & tube design. Closed cell insulation.
• Special construction materials
• Heat tracing for low ambients
• Dual circuit evaporators
Compressors
Hermetic scroll or reciprocating types. Internal overload protection. Crankcase heaters and service valves.
• Semi-hermetic compressors
• Multiple circuit designs
• Dual pump lead/lag operation
Piping
Refrigerant piping is rigid copper with service valves. Insulated suction lines. Water circuit is insulated seamless heavy grade copper.
• Alternative materials for special fluids and corrosion resistance
Warranty and Certifications
One year parts, five year limited compressor warranty. ETL Listed. MEA-386-92E for metropolitan New York.
• Extended parts & labor warranty
• Guaranteed emergency response
• Factory start-up and maintenance